Overview
This article provides steps to work through troubleshooting a Chiller Not Cooling alert for the compact chiller in the Countertop 1.5 (CT 1.5).
Alert Details
The alert triggers if the ice bank temperature remains above 8 °C for 24 consecutive hours.
In this article (click to jump):
- Overview
- Troubleshooting Steps
- Task 1: Check ventilation and installation.
- Task 2: Manually clear the Chiller Not Cooling alert and check for other alerts.
- Task 3: Check the Chiller Sensor Data.
- Task 4: Test the Compressor.
- Task 5: Inspect the Compressor Power cable.
- Task 6: Exit Troubleshooting tools and confirm
Troubleshooting Steps
Task 1: Check ventilation and installation.
NOTE: Ventilation checks should be the first step for all temperature and current-related alerts for Countertop models with a compact chiller.
- Double-check the ventilation grate and proper installation of the compact chiller.
- Confirm the correct ventilation holes have been drilled in the toe kick of the cabinet.
- Confirm that the bottom of the chiller is sitting flush on the cabinet floor, with the ventilation grate feet located in the holes.
- See Poor Ventilation troubleshooting for additional details.
- Any issues with the cabinet ventilation must be addressed prior to any further troubleshooting.
- If the ventilation requirements are met, continue to Task 2.
Task 2: Manually clear the Chiller Not Cooling alert and check for other alerts.
NOTE: This step is required to unblock the compressor for troubleshooting, as (red/Severity 1) alerts will block the compressor from running. For a full list of machine alerts, see here.
- Enter the Service Panel to resolve the "Chiller Not Cooling" alert.
- Touch the service icon in the upper left corner.
- Touch “Start Service”.
- Enter the PIN to access the service panel.
- On the left side of the screen, touch “Machine Alerts”.
- Are there other alerts present?
- If YES:
- Troubleshoot and resolve other alerts (red/Sev 1) first, as the compressor is blocked due to them, and may have thrown this alert as a result.
- Restart this troubleshooting once no other alerts (red/Sev 1) are active.
- If NO: Continue to next step.
- If YES:
- Mark the “Chiller Not Cooling” alert as resolved.
- Restart the machine.
- Locate the front power switch and toggle to OFF.
- Wait 30 seconds.
- Toggle the switch back to ON.
Task 3: Check the Chiller Sensor Data.
- From the Alerts & Troubleshooting screen, select Troubleshooting Tools.
- In Data > Chiller, inspect the Chiller sensor data to verify they are reporting correctly.
- If sensor values are reported as “Unknown”, see Compact Chiller Connection Lost troubleshooting here.
- Check if the Chiller Ice Bank is full.
- If Chiller Full = YES, continue to the next steps.
-
If Chiller Full = NO, jump to Task 3a.
- Check if Ice is detected.
- If Ice Detected = NO, continue to the next steps.
-
If Ice Detected = YES, but water is warm, jump to Task 3b.
- Check the chiller temperature.
- If the chiller temperature appears to be reading an expected value (~8-30°C), continue to next steps.
-
If the chiller temperature reads < 0.5°C, is fluctuating rapidly, above 40°C, or is “NaN”, the chiller temperature sensor or its connection may be bad, jump to Task 3c.
- If the above Chiller Sensor data points are reporting correctly, jump to Task 4.
Task 3a: If Ice Bank is LOW.
- If Chiller Full = NO, fill the ice bank.
- From the Troubleshooting Tools Menu, go to Controls > Chiller.
- Press “Start” to begin filling the ice bank. The machine will automatically start filling the chiller until the correct level is reached.
- Confirm in Data > Chiller, that Chiller Full = YES.
- If the ice bank fill fails:
- Exit the Troubleshooting Tools Menu, and resolve the Ice Bank Low Alert if present.
Task 3b: If Ice is detected, but water is dispensing warm.
- If Ice Detected = YES, but the water is dispensing warm, troubleshoot the ice sensor.
- Power OFF the compact chiller.
-
Remove the top and left side PCB panels.
- Inspect the Chiller Sensor cables for any damage between the BUC board and Ice Pins.
- Inspect the connection at the BUC board to ensure it is fully seated.
- Confirm the quick-connects are fully seated onto the Ice Sense Pins.
- Check the harness for any visible damage.
- If any damage is found on the chiller sensor cable, please contact Bevi Support at 866-704-2384.
- Carefully disconnect, then reconnect the Chiller Sense connector at the BUC board.
-
Ensure the connector is fully seated and clicks into the board side connector.
-
- After reseating, power on the Chiller and navigate back to the Troubleshooting Tools menu.
- If Ice Detected = NO, continue to Task 4.
- If Ice Detected = YES, continue to next steps.
- Test the Ice Pin cables to confirm they are working properly.
- Power OFF the chiller.
- Locate the Ice Sensor wires.
- The ice sensor signal is a red wire ending in a straight quick-connect.
-
The ice sensor ground is a gray wire ending in a right-angle quick-connect.
- Disconnect the quick-connects for the Red and Grey wires from the Ice Pins.
- You may need to release the sensor pins from the plastic clips and lift up slightly on the pin to disconnect the quick-connects.
- Power ON the chiller.
- Using a metal tool, jump the quick-connects on the red and grey wires together.
- Small needle nose pliers, a piece of wire, or a paper clip can be used to jump the connectors together.
- With an electrical connection between the red and grey wires for >1 minute, check if Ice Detected is YES or NO.
- If Ice Detected remains “Yes”, either the chiller sense cable or BUC Board is bad.
- Contact Bevi Support at 866-704-2384.
- If Ice Detected changes to NO then the ice sensor is working properly, continue to Task 4.
- If Ice Detected remains “Yes”, either the chiller sense cable or BUC Board is bad.
Task 3c: Check the Chiller Temperature data.
- Power OFF the Chiller.
- Inspect the Chiller Sensor cables for any damage between the BUC board and Temperature Sensor.
- Inspect the connection at the BUC board to ensure it is fully seated.
- Carefully disconnect, then reconnect the Chiller Sense connector at the BUC board.
- Ensure the connector is fully seated and clicks into the board side connector.
- Ensure the connector is fully seated and clicks into the board side connector.
- Inspect the Temperature Sensor connection to the Chiller Sensor harness.
- Inspect both the cable connector, and the temperature sensor for any visible damage to the wiring and or any corrosion.
-
If any damage is found on the chiller sensor cable or the sensor itself, please contact Bevi Support at 866-704-2384.
-
- Inspect both the cable connector, and the temperature sensor for any visible damage to the wiring and or any corrosion.
- After performing the above steps, power ON the Chiller and navigate back to the Troubleshooting Tools menu.
- If the temperature data is reporting an expected value, continue to Task 4.
- If the chiller temperature still reads < 0.5°C, is fluctuating rapidly, above 40°C, or is “NaN”, the temperature sensor or BUC board may be bad.
- Contact Bevi Support at 866-704-2384.
Task 4: Test the Compressor.
- Confirm there are no active Sev 1 Alerts.
- If any alerts are active, troubleshoot to resolve.
- From the Troubleshooting Tools screen, turn on the compressor.
- In Chiller > Controls, switch the compressor to ON.
- Check for Overcurrent LEDs.
- In the PCB panel, inspect the BUC board for Overcurrent LEDs.
- If the LEDs are red, an overcurrent has occurred.
-
Jump to Task 5 to troubleshoot.
- In Chiller > Data, check the compressor current while the compressor is on.
- If the compressor current is reading within a normal range, continue to Task 6.
- If compressor current is either in the No Power or High ranges, jump to Task 5 to troubleshoot the compressor power cable.
- If current is in the LOW range, the chiller may have a refrigerant leak and requires replacement.
| Current Readings (amps) | ||||
|---|---|---|---|---|
| Chiller Model | No Power | Low | Normal | High |
| NA (120 V) | < 0.5 | ~1 - 1.5 | ~1.8 - 2.5 | ~2.7 |
Task 5: Inspect the Compressor Power cable.
- Power OFF the compact chiller.
- In the PCB panel, locate the Compressor power cable on the BUC Board.
- Inspect the connection to see if it appears to be damaged, or not fully seated.
- Gently disconnect, and reconnect the 120 VAC Compressor power cable.
- There is a lock latch on the bottom side of the connector that needs to be depressed to disconnect the cable.
- Inspect the wiring connections to the connector itself, checking for loose pins that are not properly seated into the cable-side connector.
- When reconnecting, ensure the connector is fully seated and clicks into place.
- Once reseated, power ON the chiller.
- Navigate back to the Troubleshooting Tools menu.
- In Controls > Chiller, turn on the compressor and verify compressor current in Data > Chiller.
- If the compressor is still not turning on after confirming all the above checks, the problem is isolated to the compressor, the cables, or the BUC Board.
- NOTE: The compressor itself is not replaceable. If the BUC Board and cables have been replaced, the chiller would need to be replaced.
Task 6: Test and Confirm
- If the compressor current is within range in Troubleshooting Tools, exit TT and the service panel to allow the chiller to run.
- The compressor will turn off upon exiting TT and has a five-minute minimum off time before it can restart.
- Wait at least 5 minutes to allow the compressor to work, and for the ice bank temperature to drop.
- Bevi Support can help check the sensor data to confirm the temperature is beginning to drop.
- If not in touch with Support to read sensor data, wait at least 10-15 minutes before entering Service Panel Troubleshooting Tools to confirm the ice bank temperature has started dropping before completing service.